Installation method and quantity instruction:
1. Powder quantity:
1) Vertical installation:
Each meter of Ground rod or
Chemical ground rod need about 25kg
2) Horizontal installation:
Each meter of Ground rod or Chemical ground rod need about 15kg-30kg
2. Water percentage
Accoring the weather, water percentage about 40% water and 60% BSD Resistance Reducing Agent.
1. Horizontal Installation
Rods Length(M)
|
1
|
2
|
3
|
5
|
10
|
15
|
20
|
25
|
30
|
Quantities(KG)
|
15-30
|
30-60
|
45-90
|
75-150
|
150-300
|
225-450
|
300-600
|
400-700
|
500-800
|
2. Vertical Installation
Rods Length(M)
|
1
|
1.5
|
2
|
2.5
|
3
|
Quantities(KG)
|
25
|
37.5
|
50
|
62.5
|
75
|
Note:
b1=150--20mm
b2=100--150mm
h=150-200mm
d>=150--200mm