EN

Installation method and quantity instruction:

1. Powder quantity:
1) Vertical installation:
Each meter of Ground rod or Chemical ground rod need about 25kg
2) Horizontal installation:
Each meter of Ground rod or Chemical ground rod need about 15kg-30kg

2. Water percentage
Accoring the weather, water percentage about 40% water and 60% BSD Resistance Reducing Agent.

1. Horizontal Installation
Rods Length(M) 1 2 3 5 10 15 20 25 30
Quantities(KG) 15-30 30-60 45-90 75-150 150-300 225-450 300-600 400-700 500-800

2. Vertical Installation
Rods Length(M) 1 1.5 2 2.5 3
Quantities(KG) 25 37.5 50 62.5 75

Note:
b1=150--20mm
b2=100--150mm
h=150-200mm